ICAD Actuator

Brand: Danfoss

Actuator Types ICAD 600A And 1200A are dedicated for use with ICM motor operated valves. 

There are only two sizes of ICAD actuators that cover the range of valves from ICM 20 to ICM The ICAD is controlled Via a modulating Analog signal (e.g. 4-20 mA/2-10 V) or a digital ON/OFF signal. 

ICAD incorporates an advanced MMI (Man Machine Interface), including continuous display of opening degree, which gives the user a very advanced and flexible setup procedure that can meet many different applications.
Features
  • Designed for industrial refrigeration installations
  • Advanced and high speed Digital Stepper Motor Technology Seven segment LCD display and three programming keys included
  • Valve opening degree can be observed continuously
  • Can easily be configured to different applications on-site (change speed, ON/OFF, Fail Safe operation, modulating valve, etc.) 
  • Open – Close time: 3-45 seconds depending on valve size
  • Modulating, ON/OFF operation or Neutral zone / 3 point control
  • Multiple speed selection during operation
  • Logging of old alarms
  • Password protection
  • Control input signal: 4-20 mA, 0-20 mA, 0-10 V, 2-10 V; One or two digital inputs
  • Position feed back : 0-20 mA, 4-20 mA (ICM)
  • 3 Digital ON/OFF feedback
  • Resolution: 20 micron/step (0.02 mm stroke pr. step)
  • Total steps: 250 to 3650 depending on size
  • Auto Calibration, Neutral zone
  • In the event of a power failure, multiple fail safe options are possible. During power failure, ICM can be selected to: Close ICM; Open ICM; Stay in the same position, as when power failure occurs; Go to a specific ICM valve opening degree 
    • Enclosure: IP67 ~ NEMA 6
    • Approvals: CE, UL, CRN
    • Connectors for easy installation and servicing
    • ICAD 600A/1200A ensures an acurate feedback on the valve position.
  • Hermetic magnetic motor
  • Enclosure: IP67 ~ NEMA 6 
  • Approvals: CE, UL, CRN 
  • Connectors for easy installation and servicing 
  • ICAD 600A/1200A ensures an acurate feedback on the valve position

Models matching criteria: 5
  • Model - ICAD 600A
  • Cable - ICAD 600A with 1.5 metres (60") Cables
50+ In Stock
$1,805.00 CAD
Does not ship to OH, United States
  • Model - ICAD 1200A
  • Cable - ICAD 1200A without Cables
50+ In Stock
$2,106.00 CAD
Does not ship to OH, United States
  • Model - ICAD 1200A
  • Cable - ICAD 1200A with 1.5 metres (60") Cables
50+ In Stock
$1,631.00 CAD
Does not ship to OH, United States
  • Model - ICAD 600A
25+ In Stock
$2,428.00 CAD
Does not ship to OH, United States
  • Model - ICAD 600A
  • Cable - ICAD 600A without Cables
5 In Stock
$125.00 CAD
Does not ship to OH, United States

Specifications

Brand

Ambient Temperature Range

  • -30° to 50° C (-22° to 122° F)

Approvals & Certifications

  • BV
  • CE According to 89/336 EEC (EMC)
  • CRN
  • DNV
  • EAC
  • EMC Directive: Emission (EN 61000-6-3), Immunity (EN 61000-6-2)
  • GL
  • UL (C,US)

Cable Length

  • 5 to 49 feet to (1.5 to 15 metres)

Capacity

  • 1.5 to 10,446 KW: Nominal Capacity for Liquid Line without Phase Change
  • 2.3 to 39,671 KW: Nominal Capacity for Liquid Line with/without Phase Change

Cover Material

  • Top Cover: Low Temperature Steel (EN G20Mn5QT, EN 10213-3, ASTM LCC, A352, JIS SCPL1, G5151)

Current

  • Analog Input & Output: 0-20 mA
  • Analog Input & Output: 4-20 mA
  • Load: Max.

Electrical Connectors

  • 22 AWG - (3 x ~22 AWG)
  • 24 AWG - (7 x ~24 AWG)
  • 4-Poled M12 Female Connector
  • 4-Poled M12 Male Connector
  • 8-Poled M12 Male Connector

Enclosure, Body Material

  • Aluminum
  • Low Temperature Steel (EN G20Mn5QT, EN 10213-3, ASTM LCC, A352, JIS SCPL1, G5151)
  • PBT - Thermo Plastic

Environmental Protection

  • IP67
  • NEMA 6

Gasket Material

  • Cloroprene (Neoprene)
  • Fiber, Non-Asbestos

Indication

  • LED

Input Signal

  • Control Input Signal: 0-10 V
  • Control Input Signal: 0-20 mA
  • Control Input Signal: 2 to 10 V
  • Control Input Signal: 4-20 mA

Load

  • ≤ 250 ohms
  • 10 kiloohms
  • 200 ohms

Mounting

  • DIN Rail Mounting

NPT Connection

  • 1” NPT Female (ANSI/ASME B 1.20.1)
  • 1-1/4” NPT Female (ANSI/ASME B 1.20.1)
  • 3/4” NPT Female (ANSI/ASME B 1.20.1)

Nut & Bolt Material

  • Bolt: Stainless Steel (EN A2-70, EN 1515-1, ASTM Grade B8 A320, JIS A2-70, B 1054)

O-Ring Material

  • Cloroprene (Neoprene)

Operating Pressure

  • Maximum

Output Load

  • 50 ohms

Seat / Seal Material

  • Seat: High Density Polymer

Supply Voltage

  • 5-24 Vdc - External
  • Analog Input: 0-10 Vdc
  • Analog Input: 2-10 Vdc

Switch Type

  • NPN Transistor Output

Welded Connection

  • 1” Socket Weld ANSI (B 16.11)

Documentation

show more