Mini8 Controller
Brand: EurothermThe Mini8 Controller offers high performance control usually only found in Eurotherm panel mount PID controllers.
It is also a very competitive and compact data acquisition device.
Its modular design enables its I/O and feature set to be selected to cater for a wide range of applications from simple to complex.
The Mini8 controller is an ideal partner to a programmable logic controller.
Able to multi-drop on either serial, fieldbus or ethernet communications.
It offers an effective alternative to performing Analog measurement or loop control in a PLC.
Implementing these functions in the Mini8 controller PLC relieves it of the burden of performing Analog functions, often allowing a lower specification processor to be used.
Features- 16 Control loops
- 32 Analog inputs
- Modular and compact
- SP programming
- Maths and logic
- Remote HMI
- Modbus RTU
- DeviceNet network
- Profibus DP network
- Modbus TCP
- EtherNet/IP
- EtherCAT
- OEM Security
Specifications
Brand
Accuracy
- Current-Transformer Input Card (Factory Set Accuracy): Better than ± 2 % of Range
- Output Card (Setting Accuracy): ± 0.5 % of Reading
- Thermocouple (CJ Accuracy): ± 1° C (± 1.8° F)
- Thermocouple: ± 1° C (± 1.8° F) ± 0.1 % of Reading (Using Internal CJC)
Approvals & Certifications
- CE
- cUL Listed (File E57766)
- EMC Directive 2004/108/EC, EN 61326
- LVD Directive 73/23/EEC
Approvals & Certifications
- EN 61010
- FC (Factory Calibration Certificate)
Calibration
- Input Card Pt100 (Calibration Error): ± 0.1 ohms ± 0.1 % of Reading, 22 to 420 ohms
- Input Card Pt100 (Calibration Error): ± 0.3° C (± 0.54° F) ± 0.1 % of Reading, -200° to 850° C (-328° to 1,562° F)
- Input Card Pt1000 (Calibration Error): ± 0.2° C (± 0.36° F) ± 0.1 % of Reading, -200° to 850° C (-328° to 1,562° F)
- Input Card Pt1000 (Calibration Error): ± 0.8 ohms ± 0.1 % of Reading, 220 to 4,200 ohms
Communication
- Baud Rate: 100Base-T
- Baud Rate: 125K, 250K or 500K
- Baud Rate: 4,800, 9,600, 19,200 bit/sec
- DeviceNet: CAN, 5-Pin Standard Open Connector with Screw Terminals
- EtherCAT: Standard Ethernet RJ45 Connector
- EtherNet/IP: Standard Ethernet RJ45 Connector
- Ethernet: Standard Ethernet RJ45 Connector
- Modbus RTU: RS-485, 2 x RJ45, User Select Switch for 3-Wire or 5-Wire
- Modbus/TCP
- PROFIBUS DP: RS-485 Via Standard 9-Pin D Connector or 2 RJ45 Connectors
Consumption
- Power Comsumption: 15 W, Max.
Current
- Ananlogue Output (Output Current): 0-20 mA
- Current-Transformer Input Card (Current Input): 0-50 mArms, 50/60 Hz Nominal
- Fixed I/O Resources (Contact Current): < 1 A (Resistive Loads)
- Fixed I/O Resources, Logic Input Card (Input Current): 10 mA - Max.
- Fixed I/O Resources, Logic Input Card (Input Current): 2.5 mA Approximately at 10.8 V
- Input Card (Pt100, Pt1000 Bulb Current): 300 μA
- Relay Output Card, Max.
- Thermocouple (Input Leakage Current): < 100 NA (1 NA Typical)
Humidity
- Operating Humidity: 5 to 95 % Relative Humidity, Non-Condensing
Input
- Current-Transformer Input Card (Input Load Burden): 1 W
- Fixed I/O Resources, Logic Input Card: 24 Vdc
- Thermocouple: -77 to 77 mV
- Thermocouple8 8-Channel & Thermocouple4 4-ChanneL Thermocouple Input Card (Common Mode Rejection): > 120 dB, 47 to 63 Hz
- Thermocouple8 8-Channel & Thermocouple4 4-ChanneL Thermocouple Input Card (Series Mode Rejection): > 60 dB 47 to 63 Hz
Interval Time
- Load Failure Detection (Measurement Interval): 1 to 60 seconds
Isolation
- Channel to Channel, Isolation to System: 42 V Peek, Max.
- Relay Output Card (Channel to Channel, Isolation to System): 264 V, 230 V Nominal
Linearity
- Input Card (Pt100, Pt1000 Linearity Error): ± 0.02 ohms, ± 0.05° C (± 0.09° F)
Load
- Ananlogue Output: Max.
Mounting
- DIN Rail to EN 50022 35 x 7.5 or 35 x 15 Horizontally
- Horizontal
Operating Temperature
- 0° to 55° C (32° to 131° F)
Output
- Digital Output Card (Logic 0 Voltage Output): < 1.2 Vdc No-Load
- Digital Output Card (Logic 0 Voltage Output): 0.9 V Typical
- Digital Output Card (Logic 1 Current Output): 100 mA - Max.
- Digital Output Card (Terminal Supply Protection): Card Supply is Protected by 200 mA Selfhealing Fuse
- Output Card: 0-20 mA, 360 ohms Load, Max.
- PID Control Loop Blocks (Control Output): Analog 4-20 mA
- Relay Output Card (Min. Contact Wetting): 10 mA
- Relay Output Card (Min. Contact Wetting): 5 Vdc
- Relay Output Card, Max.
Power Supply
- 24 Vdc
Resistance
- Input Card (Pt100, Pt1000 Lead Resistance): 22 ohms, Max.
- Input Card Pt100 (Input Range): 0 to 420 ohms, -242.02° to 850° C (-403.64° to 1,562° F)
- Input Card Pt100 (Measurement Noise): 0.016 ohms, 0.04° C (32.07° F) Peak-to-Peak, 1.6 seconds Channel Filter
- Input Card Pt100 (Measurement Noise): 0.06 ohms, 0.15° C (32.27° F) Peak-to-Peak, No Filter
- Input Card Pt1000 (Input Range): 0 to 4,200 ohms, -242.02° to 850° C (-403.6° to 1,562° F)
- Input Card Pt1000 (Measurement Noise): 0.2 ohms, 0.05° C (32.09° F) Peak-to-Peak, 1.6 seconds Channel Filter
- Input Card Pt1000 (Measurement Noise): 0.6 ohms, 0.15° C (32.27° F) Peak-to-Peak, No Filter
- Thermocouple (Input Resistance): > 100 megaohms
Resolution
- Analog Output Card: 1 μA Typical
- Input Card Pt100: 0.008 ohms, 0.02° C (32.04° F)
- Input Card Pt1000: 0.6 ohms, 0.15° C (32.3° F)
- Thermocouple: 1.6 µV with 1.6 seconds Filter Time
- Thermocouple: 20-bit (∑∆ Converter)
RTD Type
- Pt100
- Pt1000
Sensor, Probe Type
- B Thermocouple
- C Thermocouple
- J Thermocouple
- K Thermocouple
- L Thermocouple
- N Thermocouple
- R Thermocouple
- S Thermocouple
- T Thermocouple
Storage Temperature
- -10° to 70° C (14° to 158° F)
Supply Voltage
- Digital Output Card (Channel Supply): 15-30 Vdc
- Power Supply Voltage: 17.8-28.8 Vdc
Temperature Coefficient
- Input Card (Pt100, Pt1000): ± 0.002 % ohms Reading/°C Ambient Change Relative to Normal Ambient 25° C (77° F)
- Thermocouple: < ± 50 ppm (0.005 %) of Reading/°C
Temperature Range
- Thermocouple (Cold Junction Range): -10° to 70° C (14° to 158° F)
Unit of Measure
- Temperature Unit: Centigrade
- Temperature Unit: Fahrenheit
Voltage
- Fixed I/O Resources (Terminal Voltage): < 42 Peek