AP7380 Field Configurable Signal Conditioner
Brand: EurothermThe Action Pak Model AP7380 is a frequency input signal conditioner with 1,500 Vdc isolation between input, output and power.
The field configurability of the input and output offers flexible, wide ranging capability for magnetic pick-ups, turbine flow meters, and other pulse or frequency output transducers.
The input of the AP7380 can be configured for any frequency span from 2 Hz (e.g., 59 to 61Hz) to 10,000 Hz.
The input amplitude threshold (SENS POT) can be adjusted from 150 mVp to 10 Vp to ensure accurate frequency measurement and minimize transient noise related errors.
The maximum input amplitude is 150 Vrms. The output can be set for either 0 to 5 V, 0 to 110 V, 0 to 1 mA or 4 to 20 mA.
Features- Field configurable input rangesfrom 2 to 10,000 Hz
- Four field configurable output ranges 0 to 5 V, 0 to 10 V, 0 to 1 mA, 4 to 20 mA
- Eliminates ground loops
- Plug-in installation
- Selectable 120/240 Vac input power
- ASIC Technology for enhanced reliability
Displaying prices & availability for Ohio, United States in CAD. Change location.
Models matching criteria: 4
100+ In Stock
$554.00
CAD
Does not ship to OH, United States
- Coating - Urethane Coating of Internal Circuitry for Protection From Corrosive Atmospheres
- Factory Calibration - Factory Calibration of Input Range, Set Points, and Output Relays
100+ In Stock
$363.00
CAD
Does not ship to OH, United States
- Coating - Without
- Factory Calibration - Factory Calibration of Input Range, Set Points, and Output Relays
50+ In Stock
$593.00
CAD
Does not ship to OH, United States
- Coating - Urethane Coating of Internal Circuitry for Protection From Corrosive Atmospheres
- Factory Calibration - Without
50+ In Stock
$1,532.00
CAD
Does not ship to OH, United States
Specifications
Brand
Accuracy
- ± 0.1 % of Selected Range at 25° C (77° F)
Approvals & Certifications
- CSA C22.2 No. 0-M91 & 142-M1987 (File No. LR42272-64)
- IEC 801-2, Level 2 (4 kV)
- UL (C,US), UL 508 (File No. E99775)
Consumption
- Power Consumption: 2 W Typical
- Power Consumption: 3 W, Max.
Display
- LED Display
Electrical Connectors
- 8-Pin
Electromagnetic Rating
- ESD Protection
Frequency
- Frequency Input (Full Scale Range): 2 to 10,000 Hz
- Input (Over-Range): 20 kHz, Max.
- LED Indication: Input 107 % Then 8 Hz Flash
Humidity
- Operating: 15 to 95 % Non-Condensing at 45° C (113° F)
- Soak: 90 % Non-Condensing for 24 Hours at 65° C (149° F)
Hysteresis
- ± 0.1 % of Selected Range at 25° C (77° F)
Input
- 0 to 1,000 Hz
- Amplitude Range: 150 mVp-10 Vp
- Amplitude Range: 150 Vrms, Max.
- Common Mode (Input to Ground): 1,500 Vdc, Max.
- Overvoltage: 180 Vrms, Max.
Input Impedance
- > 10 kiloohms
Isolation
- 1,500 Vdc between Input, Output & Power
Linearity
- ± 0.1 % of Selected Range at 25° C (77° F)
Mounting
- DIN Rail
- Track/Surface
Operating Temperature
- -15° to 60° C (5° to 140° F)
Output
- 0-10 V
- 0-20 mA
- Compliance (0-1 mA): 10 V, Max.
- Compliance (4-20 mA): 20 V, Max.
- Drive: 10 mA - Max.
Output Impedence
- Current: > 100 kiloohms
- Voltage: < 10 ohms
Power
- Selectable 120/240 Vac (± 10 %, 50/60 Hz)
Response Time
- 10-90 %: 3 Input Cycles Plus 250 milliseconds
Sensitivity
- 1 V Peak (LO)
Span & Zero Adjustments
- Zero Turn-Up (9998 Hz), Span Turn-Down (2 Hz): 99 % of Full Scale
Stability
- ± 0.025 %/°C, Max.
Storage Temperature
- -25° to 70° C (-13° to 158° F)