Approvals & Certifications
- CSA C22.2 No. 0-M91 & 142-M1987
- UL (C,US)
- UL 508
Output Ranges
- 0-20 mA
- 4-20 mA
- 0-5 Vdc
- 0-10 Vdc
Output Accuracy
- Current Outputs: + 0.1 % of Full Scale Max.
- Voltage Outputs: + 0.1 % of Full Scale Max.
Stability
- +100 ppm (± 0.01 %) of Full Scale/°C
Response Time
- 250 Millisecond Typical
- 300 Millisecond Max.
Temperature Range
- 0° C to 60° C
- 32° F to 149° F